Product SKU: HM-TD6368-50C4L/G0/T2Y
Product Overview
The Hikvision HM-TD6368-50C4L/G0/T2Y Thermal & Optical Bi-Spectrum Network Positioning System is a specialised long-range thermal PTZ solution designed for early fire detection, smoke detection, perimeter protection and surveillance across very large outdoor environments. It combines a high-sensitivity 640 × 512 thermal channel with a 50mm thermal lens and a separate 4MP optical camera featuring a 6–336mm motorised lens with 56× optical zoom. Long-range laser illumination up to 2,000m, continuous 360° PTZ positioning, temperature monitoring and intelligent thermal analytics make it suitable for industrial sites, bushfire monitoring, mining operations, ports, substations, waste facilities and critical infrastructure.
Key Capabilities
Long-Range Fire Detection
Dynamic thermal fire-point detection can identify up to 10 fire points, with project reference figures indicating detection of a 1m × 1m fire target from approximately 2,000m under suitable conditions.
Smoke Detection up to 6km
Hikvision specifies smoke detection capability up to approximately 6km for a reference smoke target measuring 5m × 5m.
640 × 512 Thermal Imaging
The 12 μm VOx thermal detector with NETD ≤20 mK provides sensitive heat-signature detection for darkness, difficult lighting and large-area monitoring.
56× Optical Zoom
The separate 4MP optical channel uses a 6–336mm motorised lens to provide detailed visual verification of distant targets and thermal events.
2,000m Laser Illumination
Long-range laser illumination supports optical surveillance of distant targets at night, with illumination intensity and angle automatically adjusted.
Temperature & Perimeter Analytics
Supports temperature exception alarms, line crossing, intrusion, region entrance and region exit analytics for combined fire-prevention and security applications.
Best For
- Bushfire & Wildfire Monitoring: Monitor large areas of bushland, forestry or vegetation for developing heat sources and visible smoke.
- Mining & Industrial Sites: Detect fire, abnormal temperatures, people and vehicles across large remote facilities.
- Waste & Recycling Facilities: Monitor combustible stockpiles and waste areas where heat build-up may indicate an emerging fire.
- Solar Farms & Substations: Combine temperature monitoring, perimeter security and long-distance visual verification.
- Ports & Critical Infrastructure: Provide long-range surveillance across docks, storage areas, restricted zones and large infrastructure sites.
Why Choose the HM-TD6368-50C4L/G0/T2Y
Choose the Hikvision HM-TD6368-50C4L/G0/T2Y when a project requires considerably more than conventional CCTV. Its thermal channel can identify heat signatures independently of visible lighting, while the optical PTZ channel allows an operator to zoom in and visually investigate detected events. The system is particularly valuable for sites where detecting a developing fire, smoke plume, perimeter intrusion or distant vehicle as early as possible can significantly improve response time. Continuous 360° rotation, long-range laser illumination and intelligent positioning allow a single unit to patrol and investigate very large areas.
Buyer Decision Tips
Fire Detection Example: For project planning, a fire measuring approximately 1m × 1m may be detectable from around 2,000m under suitable reference conditions. Actual range depends heavily on fire intensity, target size, weather, terrain, viewing angle and line of sight.
Smoke Detection Example: Hikvision specifies smoke detection up to approximately 6km using a 5m × 5m reference smoke target. This makes the camera particularly useful for monitoring bushland, industrial sites and large open areas where early smoke detection is required.
Thermal Lens Note: The fixed 50mm thermal lens provides an approximately 8.7° horizontal × 7.0° vertical field of view. It is designed primarily for long-range detection rather than broad short-range coverage.
Power & Installation: This is a large professional positioning system with maximum power consumption of approximately 150W. Structural mounting, power, network infrastructure, lightning protection and access for servicing should be considered during project design.
Key Features & Technical Specifications
| Product Type | Thermal and optical bi-spectrum network PTZ positioning system. |
| Model | HM-TD6368-50C4L/G0/T2Y. |
| Brand | Hikvision. |
| Primary Applications | Fire prevention, smoke detection, temperature monitoring, perimeter protection and long-range surveillance. |
| Thermal Detector | VOx uncooled focal plane array. |
| Thermal Resolution | 640 × 512. |
| Pixel Interval | 12 μm. |
| Thermal Sensitivity | NETD ≤20 mK at 25°C, F# 1.0. |
| Thermal Lens | 50mm fixed, athermalised focus. |
| Thermal Field of View | Approximately 8.7° horizontal × 7.0° vertical. |
| Minimum Thermal Focusing Distance | Approximately 33m. |
| Thermal Digital Zoom | 2×, 4× and 8×. |
| Optical Image Sensor | 1/1.8-inch progressive scan CMOS. |
| Optical Resolution | Up to 2688 × 1520, approximately 4MP. |
| Optical Lens | 6–336mm motorised zoom lens. |
| Optical Zoom | 56×. |
| Optical Digital Zoom | 2×, 4×, 8× and 16×. |
| Optical Field of View | Approximately 55.2° to 1.84° horizontal. |
| Minimum Illumination | Colour: 0.002 lux; B/W: 0.0002 lux; 0 lux with supplementary illumination. |
| Wide Dynamic Range | 120 dB WDR. |
| Laser Illumination Distance | Up to approximately 2,000m. |
| Fire Detection | Dynamic fire-point detection with up to 10 fire points detectable simultaneously. |
| Reference Fire Detection | Approximately 2,000m for a 1m × 1m reference fire target under suitable project conditions. |
| Smoke Detection | Up to approximately 6,000m using a 5m × 5m reference smoke target. |
| Temperature Measurement | Supports point, area and line-based temperature measurement rules. |
| Temperature Range | Approximately -20°C to 150°C. |
| Temperature Accuracy | Approximately ±8°C under specified conditions. |
| Perimeter Protection | Line crossing, intrusion, region entrance and region exit. |
| Human VCA Reference Range | Up to approximately 650m. |
| Vehicle VCA Reference Range | Up to approximately 1,500m. |
| PTZ Pan Range | 360° continuous rotation. |
| PTZ Tilt Range | Approximately -85° to +85° with auto flip. |
| Pan Speed | Configurable from approximately 0.01°/s to 110°/s. |
| Tilt Speed | Configurable from approximately 0.01°/s to 50°/s. |
| Presets | Up to 300 presets. |
| Patrols | 8 patrols with up to 32 presets per patrol. |
| Patterns | 4 programmable pattern scans. |
| Picture-in-Picture | Supports display of the thermal image within the optical channel. |
| Image Stabilisation | Electronic image stabilisation supported by both channels. |
| Video Compression | H.265, H.264 and MJPEG depending on stream. |
| Thermal Colour Palettes | 15 selectable palettes including White Hot, Black Hot, Fusion, Rainbow, Ironbow and Red Hot modes. |
| Local Storage | MicroSD/SDHC/SDXC card support up to 512GB plus supported NAS storage. |
| RTSP | Supported for network video streaming and compatible third-party integrations. |
| ONVIF | Published support includes ONVIF Profiles S, G and T. Additional integration capability may depend on firmware and third-party VMS requirements. |
| Compatible Hikvision Software | iVMS-4200 and Hik-Connect, with Hikvision platform integration supported. |
| Alarm Inputs | 7-channel alarm inputs. |
| Alarm Outputs | 2-channel relay outputs. |
| Audio | Audio input and output supported. |
| Network Interface | RJ45 10/100 Mbps Ethernet. |
| RS-485 | Supported. |
| Cybersecurity | Built-in TPM 2.0 encryption module plus supported network security functions. |
| Power Supply | 36V DC ±20% or 48V DC ±20% via two-core terminal connection. |
| Maximum Power Consumption | Approximately 150W maximum. |
| Operating Temperature | Approximately -40°C to 70°C. |
| Operating Humidity | 95% or less. |
| Weather Protection | IP66. |
| Environmental Protection | NEMA 4X with anti-corrosion coating. |
| Self-Cleaning System | Built-in self-cleaning module and wiper for demanding outdoor installations. |
| Surge Protection | TVS 6000V lightning protection, surge protection and voltage-transient protection. |
| Dimensions | Approximately 543.8 × 399.7 × 390.3mm. |
| Weight | Approximately 27.5kg. |
| Installation Requirements | Professional structural mounting, suitable DC power supply, network connection, surge protection and appropriate recording or VMS infrastructure are recommended. |
Ideal Use Cases
Bushfire & Forest Monitoring
Monitor vegetation, forestry and remote land for developing fire points and large smoke plumes from an elevated surveillance position.
Waste & Recycling Sites
Detect unusual heat and developing fire conditions around combustible waste, recycling material and stockpiles.
Mining & Heavy Industry
Combine thermal detection, long-range PTZ viewing and perimeter analytics across mines, processing facilities and large industrial sites.
Solar Farms & Power Infrastructure
Monitor large energy sites for temperature exceptions, fire risks, perimeter breaches and distant activity.
Ports & Logistics Facilities
Use thermal detection, long-range zoom and continuous PTZ coverage across container areas, docks, storage facilities and restricted zones.
Remote Perimeter Protection
Detect human and vehicle activity across long fence lines and remote boundaries, including environments with little or no visible lighting.
Choosing the Right Model
- Choose this model if: You need one specialised camera to combine thermal fire detection, smoke detection, temperature monitoring, long-range perimeter analytics and high-powered optical PTZ surveillance.
- Choose the 50mm thermal version for: Long-range monitoring where a relatively narrow thermal field of view is preferred over broad short-distance coverage.
- Consider another thermal lens for: Projects requiring a substantially wider thermal scene or different detection geometry.
- Do not treat reference distances as guarantees: Fire, smoke, human and vehicle detection distances depend on target size, temperature, weather, installation height, background conditions, terrain and line of sight.
- Plan supporting infrastructure: Allow for structural loading, up to 150W power consumption, networking, lightning protection, recording or VMS integration and safe maintenance access.
FAQs
-
- How far can the HM-TD6368-50C4L/G0/T2Y detect a fire?
For project planning, a fire target measuring approximately 1m × 1m may be detectable from around 2,000m under suitable reference conditions. This is not a guaranteed detection distance because actual performance depends on the fire size and intensity, weather, terrain, line of sight and installation conditions.
- How far can the HM-TD6368-50C4L/G0/T2Y detect a fire?
-
- How far can it detect smoke?
Hikvision specifies smoke detection capability up to approximately 6km using a 5m × 5m reference smoke target. Actual detection distance will vary with the density and size of the smoke plume, weather, background and viewing conditions.
- How far can it detect smoke?
-
- Can it detect more than one fire at a time?
Yes. The intelligent fire-detection function supports dynamic detection of up to 10 fire points.
- Can it detect more than one fire at a time?
-
- Does the camera work in complete darkness?
Yes. The thermal channel detects heat signatures rather than relying on visible light. The separate optical camera also has long-range supplementary laser illumination for night-time visual verification.
- Does the camera work in complete darkness?
-
- How far can the optical camera see at night?
The optical channel provides long-range laser illumination rated up to approximately 2,000m. The distance at which a person, vehicle or object can actually be identified will depend on zoom position, atmospheric conditions, target size and reflectivity.
- How far can the optical camera see at night?
-
- What is the difference between the thermal and optical channels?
The thermal channel uses a 640 × 512 heat-sensitive detector and 50mm lens to detect temperature differences and thermal targets. The optical channel provides conventional 4MP video with a 6–336mm motorised lens and 56× optical zoom for detailed visual verification.
- What is the difference between the thermal and optical channels?
-
- Can it detect people and vehicles?
Yes. Intelligent perimeter protection supports human and vehicle-related applications. Reference VCA ranges are approximately 650m for humans and 1,500m for vehicles under suitable conditions.
- Can it detect people and vehicles?
-
- Can the HM-TD6368 measure temperature?
Yes. It supports point, area and line-based temperature measurement rules with temperature exception alarms that can be used as part of a fire-prevention strategy.
- Can the HM-TD6368 measure temperature?
-
- Can the camera integrate with a third-party VMS?
The camera supports RTSP, Hikvision APIs and published ONVIF interoperability including Profiles S, G and T. Compatibility with specific VMS analytics, metadata and alarm functions should be confirmed for the intended platform and firmware version.
- Can the camera integrate with a third-party VMS?
-
- Is the camera suitable for exposed outdoor installation?
Yes. The system is rated IP66 and NEMA 4X and includes anti-corrosion protection, a wiper, self-cleaning functionality and surge protection for demanding outdoor environments.
- Is the camera suitable for exposed outdoor installation?
-
- What power supply does it require?
The camera supports 36V DC or 48V DC within the specified tolerance and can consume up to approximately 150W. Power design should be confirmed before installation.
- What power supply does it require?
- What should I check before purchasing this camera?
Confirm the required thermal detection distances, smoke and fire detection objectives, mounting height, target areas, line of sight, structural support, available power, network connectivity, recording requirements and VMS integration. For critical fire-detection applications, a project-specific site assessment is recommended rather than relying solely on maximum published detection distances.
Additional Information